Gas Copper Neva Suite 8224 Error 03. Systems of heating of country and country houses. Boilers, gas speakers, water heaters - repair, service, operation. Installation and installation recommendations. The temperature is supplied in the system lower than setting

NEVA heating equipment is one of the most popular among users. The technique of this brand has been adapted to Russian realities, steadily works under reduced pressure in the highway. But this does not mean that exploitation costs without breakdowns. Errors of the "Neva Suite" boiler will indicate malfunctions in the system, and their value will help restore the operation of the equipment.

Features of the operation of the "Neva" boilers

The gas boiler "Neva" is represented in the wall and outdoor option. Single-mounted devices can drop the area in 180 m², differ in low energy consumption. Function on the main and liquefied fuel. Since the combustion chamber has aqueous cooling, it is possible to connect to an outdoor thermostat. The chimney organization is carried out to the main mine or turbocharger.

Dual-circuit units are represented by the "Neva Lux" models. The design includes two heat exchanger for heating and hot water supply (DHW). For example, a Bi-Letter Radiator is built into the "Neva Suite 7224" model. This tube in the tube, where water is simultaneously heated for two contours.

Control of instruments mechanical and electronic. Special sensors control the operation of the boiler, the signal is sent to the control module. Then the display displays the display. To find out its value, you can look into the instructions.

NEVA technology error codes

We list the main fault of the device, as well as specify the troubleshooting options.

NEVA LUX errors

Fault code What means How to repair
e1 / 04. The heating system reduces pressure.
  • Switch the air from the contour, increase the pressure.
  • Diagnose the bypass valve. Switch the work on heating area, close the valve into the system. Water should go through the bypass highway, otherwise the item is faulty.
  • Rinse the pump from the zero, with a malfunction, replace.
  • Repair of the pressure sensor chain. Inspection of connectors, cables.
  • Check the sensor rod for sticking. Turn off the device and dismantle the sensor and rod. If the membrane is damaged, install a good item.
  • The duct sensor failed. Spend diagnostics and replacement.
  • Inspect the engine of the three-way valve.
e2. Ignition error. What to do:
  • Unscrew the shut-off valve until you stop.
  • Replace the cylinder of liquefied gas.

Spend inspection and replacement when breakdown:

  • Candles ignition and its wiring.
  • Wiring ionization. To do this, remove the wire from the candle - the work must be blocked, and the display will appear on the display. Connect the wire again, hold the K6 buttons and reboot.
  • Transformer ignition and its chains.
  • Gas supply regulator.

Also remove the dust from the candle, move it closer to the burner (3 mm). Replace the control fee

e6 / 03. There were problems with the burden.
  • Clean the chimney from garbage and soot.
  • Inspect the tubes leading to the pressost. If they scored, clean them from condensate or put new ones.
  • Diagnostics of the press service and its wiring.
  • Check the fan and its chain.
e7. The water temperature exceeds the norm. How to proceed:
  • Remove the zoom from the heating system.
  • Make sure the thermostat is correct, check whether it shows the exact temperature.
  • Open the valve and run the excess air.
  • Clean the filter from dirt, garbage, rust.
  • Check the location of the bypass.
  • The pump does not turn on. Perform repair.
  • Replace the item that adjusts the fuel supply.
  • Connect the S3 switch properly on the electronic module.
01 Razhigih fails. How to fix the problem:
  • Make sure that the gas crane is properly opened.
  • Candle ignition has emerged or clogged. Clean the detail from dust. If the candle or its wiring is faulty, swipe.
  • Adjust the distance between the candle and the burner (3 mm).
  • When the electrode is turned on, the spark is beating on the combustion chamber. Isolate breakdown space.
  • Measure the ionization current. Connect the microammeter to the ionization chain, measure the indicators. Normally should be from 3 to 5 microampers.
  • Inspect the ignition transformer chain. Repair.
  • Remove the soot from the combustion unit.
02 Technique does not work due to overheating.
  • The heating circuit is clogged. Perform cleaning.
  • Install a good thermaller.
  • Passe air with cranes.
  • Clean the heating filter from garbage.
  • Incorrectly mounted bypass valve. Reconnect item.
  • Faulty pump that removes excess air. Diagnostics.
  • Adjust the gas supply regulator.
05 The thermal sensor contour is broken. Check the loop from the sensor to the electronic board. Connect the new item.
06 Mallings with the temperature sensor of hot water supply.
07 The coil of the fuel supply regulator failed.
  • Measure the coil resistance to the multimeter. In operating mode there should be 80 ohms.
  • The contacts between the coil and the electronic circuit are disturbed. Check the electrical circuit.
99 Mallings with electricity.
  • Not organized grounding.
  • Truck on the boiler housing.
  • Turn the plug in the outlet

Other problems

Not all breakdowns are displayed by error codes. Some can be determined by signs.

The boiler does not turn on.

  • Check the availability of electricity if the boiler connects to the network.
  • The fuse does not work in the electronic board.
  • Circuit board due to leakage. Inspect all nodes and parts to flow.

The device creates when the ignition.

  • The ignition power or pressure is incorrectly configured. Adjust the settings.
  • Clean the chimney, ensure normal ventilation indoors to maintain traction.
  • Clean the burner block from soot and soot.

With the smell of gas indoors, shut steps the shut-off valve. Contact the gas service.

Weak water pressure when opening a mixer.

  • Pressure fell in the highway. Wait for recovery or install the pump.
  • Remove pollution and scale from the water filter and the heat exchanger parts.

The temperature of the coolant exceeds the specified.

  • Dilute the hot stream cold, increase the circulation rate.

The standby mode turned on, the panel does not function, the "-".

  • Cause in voltage drops on the network. As soon as it restores, the technique will resume work. It is recommended to install a stabilizer.

After reading the fault codes, you can proceed to eliminate or contact the service center. Good luck!

Popular gas equipment - heaters, columns, gas stoves and boilers for more than 50 years produced by the gas apparatus plant located in St. Petersburg. After the creation of the Concern "Baltic Gas Company", the company entered its composition, retaining production facilities and specialization. The current name of the company is "Neva". It is rapidly developing and produces high-tech boilers equipped with modern automation. For example, the popular and demanded series is the gas boilers of the Neva Suite, which is represented by two categories.

The model range of popular gas boilers manufactured by Neva includes two basic series: suite and turbo. In this article, consider the most famous and popular series of suite, which is divided into two categories:

The most popular NEVA LUX series boilers

Under the brand name "Neva", modern luxury gas boilers are produced, which eliminated the shortcomings of the models produced earlier. Modified design, installed modern automation, but the price of products is less similar to the parameters of models of Western companies. With other models of gas boilers, domestic production can be found in our article.

Luxury Neva model 8618

On the gas boilers, the Neva Suite price depends on the model. Single models are cheaper, dualkets are more expensive. For example, one of the most popular models of this series of the NEVALUX 8618 gas boiler is in demand due to a small price and the following qualities and capabilities:

Popular Single-Roise Gas Copper Deluxe 8618 for the wall flooring is intended only for heating, but if necessary, the DHW organization is possible with the help of an indirect heating boiler. The model has the most simple design with non-volatile automation. The price of this boiler is the lowest from the entire model range.

Luxury Neva model 8224

Wall Copper Gas Elevation Suite 8224 is designed for the heating of rooms up to 250 m2. The boiler is equipped with a unique combustion chamber of water cooling. The high accuracy of the temperature setting provides a special microprocessor. In its parameters, Nevva's boilers are not inferior to foreign samples, the only difference that has a gas boiler Neva Suux 8224 Price Reviews of many owners confirm this.

This model has two heat exchanger. A plate heat exchanger is applied to the DHW, and a copper heat exchanger is used for the heating circuit, built into the Gas Suite Suite Gas Suite of this series.

In the model it is possible to use a PC for diagnostics and configuration, as well as remote control.

On the popular gas boiler Never Suite 8224 Reviews found on the network fully confirm excellent consumer quality instruments. Many reviews emphasize that there is a relatively small in the Gas Copper of the Neva Luxury, the price is relatively small with high performance qualities. This is a wall-mounted two-circuit model, which is designed to heat the rooms up to 240 m2. The unit provides hot water supply (DHW).

Constructive components

From a technical point of view, the NEVA Navy Gas Copper is flawless. It implements all technical achievements in heat engineering, as well as developing in the field of electronic control of heating contours.

Constructive boiler Gas double-circuit neva consists of the following systems related to each other:

Advertising on the Internet and on television Calls on to buy a boiler Gas double-circuit wall-mounted luxury, as the most economical, cheapest, convenient, etc. Is it possible to believe this advertisement and reviews on web pages online shopping?

How to buy a gas boiler and not mistaken?

Buyer, choosing, for example, Wall-mounted gas boiler Suite Suite 8224 Reviews on which may be unturined and written in order, should understand that they cannot be reed. After all, it often happens that the design is ideal, the size of the most modern, but poor-quality assembly worsens all the advantages. For example, in 2014, the NEVA LUX 8224 wall gas boiler is characterized as a natural raw product, which is called - finalize with a file.

Such a review appeared due to poor-quality assembly, as well as in connection with the unstable work of the boiler due to the flaws of the coaxial chimney, which was not specified in the instructions. Of course, at present, Neva has taken certain measures and eliminated disadvantages when assembling the product. There are practically no complaints on the luxury model 8618 and buy a gas boiler Single-mounted Wall Neva Suite, and with delivery to any region, you can in specialized stores.

Prices depend on the hinged gas boilers depend on their power, type, configuration and demand for the device. For example, by many online stores a gas double-circuit wall-mounted luxury boiler, the price of which is 24 kW at a capacity, but with different complete set ranges from 31,800 to 35,600 rubles.

The most expensive NEVALUX 8224 boiler is equipped with a built-in cumulative boiler. When choosing a heating boiler if it is satisfied with the NEVA Lux Copper 8224 Price Reviews are best obtained from real owners or gas equipment professionals.

Faults of the Gas Copper Deluxe

The simplest single-circuit and non-volatile model of the Neva Luxury 8618. It completely absent electronics. A simple NEVA gas boiler is very reliable.

The most common faults are characteristic of this boiler are as follows:

  • very low gas pressure level in highway;
  • low pressure due to the availability of air in the circuit;
  • swelling flame burner;
  • mechanical damage to the boiler or heating contour.

The presence of 8224 control units with a microprocessor with a microprocessor control unit 8224 allows you to produce self-diagnostics of faults that occurred when the gas boiler is operational. Electronics, which is installed on the boiler Gas dual-circuit wall Neva Luxury Luxury displays an error code.

Error codes displayed on display

Any technical device may break. It is not an exception and boiler of the Suite of any model. Its stop can be associated with the failure of any element in the management system or their incorrect work. The error code of the control system displays, and the knowledge of the error code facilitates the malfunctional detection.

The following error codes are displayed on the display:

Error 01. This error speaks about the unsuccessful ignition. The boiler does not turn on:

Error 02. Overheating of the coolant. The boiler does not work:


Error 03. No thrust:


Error 04. Low water pressure in the circuit:


Error 05. Heating System Temperature Sensor Failure:


Error 06. Failure of the DHW temperature sensor:

  • sensor malfunction;
  • open or closing the electrical circuit between the sensor and the electronic board.

Other malfunctions that cannot be displayed. For example, if there is no electricity, the boiler will not turn on, and it will not work. Of course, if you install, then such trouble will be avoided.

Fuse blocked. The fuse rarely burns out for no reason. If after replacing the similar fuse again burned, then you need to find the cause. In no case cannot be installed "bugs", which can output all the boiler electronics.

If the e-board was accidentally filled with water. You need to turn off the boiler from the network and drip the board with warm air from the hair dryer. Sometimes there may be a failure in the operation of electronics. To install in the initial position, click the RESET button. If it did not help, then disable the boiler from the network for several minutes and turn on again.

When the smell of gas appears, you need to immediately find and eliminate leakage.

If you cannot eliminate leakage yourself, it is recommended to call the gas service for emergency telephone 104.

What does the error of 01 mean, how to eliminate faults when repairing a suite suite?

Dual-circuit gas boilers Evva Lux 8624, 8230, 8224 are a wall apparatus with forced circulation of coolant (water or antifreeze). Repair and maintenance of NEVA Luxe boilers are made according to the service instructions by a specialized service organization, which is also engaged in installing, commissioning and service work with the supply, replacement for new spare parts of this heating equipment of the suite.

So, in case of error 01 in the combustion chamber, there is no ignition of the flame or ignition begins, but it turns out unsuccessful - the kittel does not work. In this case, in this case one or at the same time several reasons for the error 01 may be present. Consider all the causes of an emergency and we will give the full volume of recommendations for the repair of the gas boiler of the Neva Suite when an error occurs 01. Technical information is submitted for service engineers of gas equipment repair organizations.

Error 01 in the electronic control board is often found when repairing gas boilers from various manufacturers of heating electron-dependent electronic control techniques. The first common malfunction is the absence of ignition - this is the incorrect operation of the entire chain of energy-dependent and mechanical actions, ranging from the pilot and ending with the main gas burner. Similar problems During the occurrence of error 01, Wisman Witopend 100, Bakci, Kituri, Electrolux, Ariston, Immergaz, Eva Suite 8224 and other models of various manufacturers. With an external inspection of the gas equipment, it is necessary to make sure that all the recommendations of the manufacturer on the installation of a gas boiler are observed: electricity, electronics, gas, chimney, air flow, correctness of the installation of the NEVA luxury boiler on the mounting scheme and the rules of gas economy.

Repair of the gas boiler Neva Suite with error information 01 begins with checking gas supply to the reinforcement of the heating boiler. Next, check all RT to the working condition, observing the contact ability of the relay. Diagnostics of the gas valve-modulator, a static and dynamic pressure check. By default, ignition elements, ionization are subject to verification and maintenance. At the same time, the gaps regarding the burner section on two electrodes should be observed. Eliminate breaks and mechanical damage that prevent the right boiler settings. Diagnosis of the ignition transformer block (coil), if there is no power to the ignition electrode.

During the repair of the Cotelet of the Neva Suite, working on liquefied gas, it is necessary to prepare documents for the last gas station of the Gazagolder (technical data of fuel), the contract for those. Maintenance boiler service and call a service specialist for the diagnosis and repair of gas. apparatus.

Timely, permanent service of the gas boilers of the Neva Suux gives uninterrupted work technique, warmth and comfort in your homes. Conducting planned repairs, the necessary replacement of spare parts you extend the life of the boilers of the suite of the suite and make the right investment.


Gas wall boilers Buderus
Models Logamax U042, U044, GB072, GB172. With an open and closed combustion chamber. Methods of repair and service, adjustment of operating parameters. Maintenance recommendations.
Gas heating boilers Vaillant
Models: Outdoor Atmovit Exclusiv, Wall Condensation Ecotec Plus. Service, maintenance, settings for functional components. Hydraulic schemes.
Gas wall boilers Ariston
Models Clas, Clas Evo, Genus. Recommendations for repair, maintenance and service. Troubleshooting errors and faults. Setup and adjustment methods.
Gas boilers Immergaz
Models Eolo Star, Eolo Mini, Nike Star, Nike Mini, Mitos. Repair and adjustment. Installation, Installation and Connection. Settings operating modes and additional equipment.
Boilers Kentatsu Furst.
Nobby Smart wall models. Condensation SMART CONDENS. Outdoor Sigma, Kobold. Solid fuel Elegant, Vulkan. Faults and error codes. Description and characteristics.


Errors of the boiler of the Neva Suite and their meanings

Error 01 (E2) - problem associated with unsuccessful ignition or overheating coolant. The boiler does not function.

Code 01 For Sound Luxury models 7023, 7224, 8224. E2 code - Evva Suite 8023, 8029.

Torget burner. Clean the burner and nozzle. The electrode of the ignition is defective, its electrical circuit is broken, the wrong gap between the ignition electrode and the burner section. Check the electrical circuit and contacts, set the correct gap (4-5 mm). Replace the ignition electrode. Fault of the wareplace transformer or its electrical circuit is impaired. Check the electrical circuit and connector contacts in the control unit. Check and, if necessary, replace the transformer. The ionization electrode is defective, its electrical panel is broken, an incorrect gap between the ionization electrode and the burner section. Perform an inspection of the electrical circuit and contacts, set the correct gap (3-3.5 mm). Replace ionization electrode. Also, when error 01 (E2) can work the coolant overheating sensor in heating mode. Find and eliminate the cause of the overheating of the coolant. Faulty coolant overheating sensor or its electrical circuit is impaired. Check the electrical circuit and contacts. Inspect the overheating sensor (must be closed at temperatures to
95С). The absence of a flame as a result of the non-gas valve. Check the presence of contact in the valve connector and in the control unit. If necessary, replace the valve.

Error 02 (E7) - overheating of the coolant

Code 02 for models 7023, 7224, 8224. Code E7 - Models 8023, 8029.

The fan is damaged (the engine winding burned down, the bearing jammed, the impeller is shrouded, the electric fan power circuit is broken). Check the integrity of the chain and contacts in connections. Provide free rotation of the impeller. If necessary, replace the fan. Also, when error 02 (E7), the coolant overheating sensor can be facped or its electrical circuit is impaired. Check the electrical chain and contacts. Check the overheating sensor (must be closed at temperatures up to 95C). Worked the coolant overheating sensor in heating mode. Find out and eliminate the cause of the coolant overheat.

Error 03 (E6) - malfunction in the combustion product removal system

Code 03 for models 7023, 7224, 8224. E6 code - model 8023, 8029.

Drying chimney or supply air canal. Clear pipes. Damaged tubes or air pressing housing are damaged. Eliminate damage or replace the tubes. The electrical press of the air press service was disturbed. Faulty air press service. Check the integrity of the chain and contacts in the connections. Replace the sensor.

Error 04 (E1) - lack of water pressure or lack of circulation in the heating circuit. The device does not start.

Code 04 for models 7023, 7224, 8224. Code E1 - Models 8023, 8029.

Small amount of water in the heating system. Pull the heat carrier in the heating circuit to the required pressure. In the heating system there is air. Remove air from the heating system. Zoom filter-mud in the heating circuit. Perform filter cleaning. The valve-bypass is defective or incorrectly. Perform check and, if necessary, replace the valve. Circulating pump failure. Replace the pump. In another error 04 (E1), there is insufficient mobility or overlooking the rod of the duct sensor in the heating circuit transmitting the movement of the microswitch, the gap of the duct sensor membrane. Remove the microswitch from the drive sensor housing. Re-enabling and turning off the boiler (turn on and off the pump) to release a fixed rod; If it did not help check the integrity of the membranes on the duct sensor. The microswitch is defective, or the electrical circuit between the microswitch and the control unit is broken.
Check the electrical circuit and contacts in the control unit connector. Replace microswitch. Failure of the drill servomotor of the three-way valve. Replace servo. Gas feed broke. Check the presence and pressure of gas at the inlet to the gas unit. Press the reset button. Incorrect phase compound when the unit is attached to the electrical outlet. Perform the correct phase connection.

Error 05 (E3) - Heating Contour temperature failure. The device does not work in the heating mode or in the DHW mode.

Code 05 for models 7023, 7224, 8224. E3 code - Models 8023, 8029.

The heating circuit temperature sensor is defective. Replace temperature sensor. Disruption of the electrical circuit Temperature sensor - control unit. Check the electrical chain and contacts.

Error 06 (E4) - DHW temperature sensor is damaged. The boiler will continue to work in heating mode and in hot water mode.

Code 06 for models 7023, 7224, 8224. E4 code - Models 8023, 8029.

Malfunction of the DHW temperature sensor. Run the DHW temperature sensor. Damage in the electrical circuit The DHW temperature sensor is a control unit. Check the electrical circuit and contacts.

E8 error - Communication error

The loop binding the controller card with the control board is damaged, or there is no contact in the plume connectors. Check the integrity of the loop and the presence of contact in the connectors. If necessary, replace the loop. Control board fault. Replace fee. Controller fees. Replace fee.

Error E9. - supply voltage for allowable boundaries

The boiler supply voltage is beyond the range of 180 - 250 V. When restoring normal supply voltage, the device will turn on automatically.

Troubleshooting

2 years I have a NEVA LUX gas boiler manufactured by Baltgaz. Now defects began to appear in his work. If you enjoy hot water for a long time, the pressure drops in the system, and it stops by error 04. Although the pressure gauge shows the same pressure of 1.6 bar. Have to
Constantly use feeding. How can I fix it?

Perhaps in your expansion tank the pressure is lower than it is supposed. It is then that an error 04 is possible.

Six months ago, I installed a dual-circuit boiler NEVA Luxury 8230. Recently faced with such a problem. When it took hot water, I as usually opened a crane. Initially, it went warm and then cold again. At this moment, a 02 error appeared at this moment. I tried to reset it with the "Reset" key, but then the heating turned on. After that, the hot water was reused in the evening. He opened the crane, and everything earned normally. 4 days the device worked without problems, but today the error appeared again. He studied more carefully. It happens so. After the transition to the heating of water for the DHW occurs, there is a sound, similar to air suction. At the same time, it is possible to observe the instability of the testimony of the pressure gauge (about 0.5 per each direction). And all this is accompanied by the same strong sound no longer only from it, but also from the membrane tank (additional, external 18l). After that, the pressure rises sharply up to 5 bar. It turns off, the water temperature drops to 23c. And error 02 is displayed. The instruction says that I have air in the heating system, but I work with DHW. What is the connection? Maybe I broke a three-way valve? Or did I have a filter in the heating system itself?

Error 02 - It overheats the coolant. Perhaps the fan broke or the sensor is damaged.

My NEVA LUX 7023 boiler approximately 2 times a month stops by error 07. The reboot always solves this problem. And now a new error has appeared - E5. It works a quarter of an hour and turns off. What happened to him?

ERROR E7 means that the coolant is too overheated. Perhaps you have a heat exchanger from the inside of the whole in scale, and because of it there is a bad circulation in the system. Did he not start it somehow unusually noise? But about E5, it is necessary to pay attention to the press service or a fan. We must look and that. In a good way, a specialist should solve this problem. Just if all in case, check may be ignored with chimney.

The unit showed an error 03. As I understood, it means problems with the fan. When checking filed voltage on it - everything is normal. Also, I checked the press service - also working. Get relays on the board? A couple of years ago came across such. But then I saw me acquainted, giving from my old unit. Tell me, can I somehow work without this relay? I tried to manually promote the fan, he started working, but the gas did not arrive. For this, the same relay is responsible? But now the error was 01.

In order for the relay longer to work, you need to more carefully adjust the gas valve and the power of heating, and it is also desirable to install a room thermostat. All this not only increases the life of the device, but also saves gas. To solve errors 01 it is required to check the voltage on the gas valve, whether it opens and whether gas enters. It is better to call a specialist, since all these checks are associated with risk for life. And the masters have a dip. Pressure gauge for gase pressure assessment. And so, most likely you have a small house and you have not been engaged in setting up a system for heated area. So the room thermostat for you is the best way out.

Help me please. In our new apartment, before us was installed wall-mounted two-door Nevalux 7218. During the day, he constantly stops by mistake 04. began to feed, then the temperature began to fall. And now the water flowed from it (in the place where heating pipe is included in it). I had to turn off. It does not work?

It is necessary to check the press service. In the chimney could clog the small tube for the air removal.

My Wall Copper Neva Suite 7023 (Baltgaz) has a problem with DHW. With heating, all the norm, and as soon as I start the analysis of the water, an E2 error appears. Water does not heat up. If the water is closed, then it is completely normal continues to dash apartments. The water pressure is consistently good. I looked in the instructions, it is written there that E2 is an error of unsuccessful ignition or overheating of the coolant. During the work of DHW, the burner begins work and burns 2 seconds. Thermometer then shows the temperature of 95C, immediately turning off the machine and the error. Water goes warm while the burner is burning. What could break?

Try checking the DHW temperature sensor, it is possible in this. Although in theory, E2 error symbolizes about problems with the ignition, but then there would be no heating.

My boiler produced Baltgaz, installed on the wall, at first did not want to switch from the heating system for hot water supply. Although, sometimes, for the reasons, he still worked as it should. First of all, he checked all the contacts to be in health, then checked the electric motor of the three-way valve. If you clamp a screwdriver, then the valve is working and works as it should. If you switch the mode (when the engine is removed), then everything works. The movement of the rod is noticeable and corresponds. He addressed the service center. The master who came to me suggested that the problem in the duct sensor. He did not see the signal to receive him. Need a new one. But I did something that the device earned. He did not work for a day, and then it took me to include it. And it does not start. The indicator blinks, all possible symbols are highlighted. Reboot did not help. Disconneted the power - also did not help. What could be the problem?

Remove the connector on the board, and alternately disconnect the wires. First of all, those that are responsible for the drive of the three-way valve. Then reinstate them again. It should solve your problem.

I can't fix the boiler Baltgaz Neva. The error 03 constantly appears, the fan does not work during the ignition. If you look at the pressost tube, it starts spinning. The device does not want to turn off on their own, you have to do it manually. How to be?

Find the hatch in the upper right corner. It needs to open and make a restart.

Other malfunctions

No spark for ignition.

Faulty or bad migration candle is installed. Properly set the candle (the gap between the candle end and the burner section is 4-5 mm) or replace it. Unreliable contact between the terminal and the ignition wire. Check the contact of the terminal with the ignition wire. Contaminated electrode ignition. Wipe the electrode from dust and degrease.

The boiler does not turn on.

No gas. Lack of water. Lack of electricity. Conduct the appropriate checks (incoming gas, water availability, connectors, fuses). Spot the nozzle burner. Clean the nozzle.
The presence of air in the gas circuit. (It may happen after long inactivity). Several times include the unit to work until an error self-sustain. Fuse blocked. Replace the fuse on the controller board. Worked the temperature sensor the heating circuit. Check the operation of the pump. If the pump is running, check the sensor. Defective gas valve. Repair or replace the valve. Deactivated boiler. Re-enable the device.

Cotton burner.

Problems in gas supply. Check the gas pressure in front of the aggregate. Contaminated burner. Check and clean the burner. Insufficient air supply. Clean the burner. Bad flame adjustment. Check the gas consumption and gas pressure in front of the burner.

The smell of gas.

Gas leakage. Check the entire gas contour for tightness using soap water or gas detector.

Small hot water outlet or her absence.

Insufficient water pressure at the entrance. Enlarge the pressure by installing an additional pump inlet. Dusty water filter. Remove and clean the filter on the DHW line. Heat exchanger with partially or completely clogged pipes. Clean heat exchanger tubes.

Cold radiators in winter.

A too low heating temperature or a thermal sensor is defective. Install a higher heating temperature or replace the thermal sensor. The pump does not work due to pollution. Remove the screw in front of the pump and turn the spindle.

Hot radiators in the summer

Winter heating mode. Set summer mode.

___________________________________________________________________________________________

___________________________________________________________________________________________

Borino, ZHMZ, Siberia, Alpha Kalor, thermal engineering.
Adjusting gas automation EUROSIT 630. Replacing the thermocouple and maintenance of the ignition burner.

2017-05-17 Evgeny Fomenko

Device and principle of work of boilers Neva Suuxe

NEVA LUX gas boilers are presented in two variations - wall and outdoor, consider their device on the example of some models. Entry Suite 8618 - a single-mounted heating boiler, a wall-mounted installation method, has a low level of energy consumption, a rather high efficiency of 91%, power of 18 kW. Can drop the room from 30 to 180 square meters.

It works both from natural and from liquefied gas. It has small dimensions, equipped with a combustion chamber, which is cooled using water, can also be connected to a room thermostat, which is convenient for use. Equipped with an overheating protection device (boiling), a thermostat from overheating of the gas traveler. It can be connected both to chimney and to the turbo nozzle.

Entry Suite 8224 is a double-circuit gas boiler, designed to heating the room with an area of \u200b\u200bup to 240 meters2, as well as for heating water for economic needs, a capacity of 14 liters per minute. Its power is 24 kW, equipped with a closed combustion chamber.

The installation method is equipped with a built-in 6 liter expansion tank, it makes it possible to connect the boiler to the heating circuit by 70 liters. The design provides two heat exchanger, copper for the heating circuit, and the second, stainless steel, for hot water supply.

It works from natural or liquefied gas, for ease of use, has a display where the current and set temperature in the coolant is reflected.

EVERA LUX 7224 - Method of installation of a wall, two-round device is designed to heat the room with an area of \u200b\u200bup to 240m2, the capacity of water for household needs 14 liters per minute. It can work on natural gas and liquefied, efficiency ratio of 92%.

Copper Neva Suuxen 7224

Equipped with a bietermic heat exchanger, due to which it is possible to reduce the final cost of heat. Equipped with an electronic system of self-diagnostics, as well as a small display installed on the case to indicate the readings.

EVERA Suite 7023 - wall mounting, designed to heating the room to 250 meters2, as well as heating of technical water 13 liters per minute. It works not only from natural gas, as well as from liquefied, for convenience, you can connect a room controller for convenience.

Deleting smoke is forcibly, with the help of a built-in fan, the air for burning fire is injected from the street. Equipped with a closed combustion chamber, has a coaxial heat exchanger, an expansion tank of 6 liters.

EVERA LUX 8023 - is a two-round wall-mounted boiler, which has the ability to provide a warm room, the area of \u200b\u200bwhich does not exceed 240 m2. The circulation of fluid in the system is forcibly, with the help of a pump, equipped with a closed combustion chamber.

Smoke removal is due to the exhaust fan. The power of the device is 23 kW, the presence of two heat exchangers is provided, the heating circuit is paramount, made of high-alloyed stainless steel.

Basic error codes

Like any other device, periodically fails, then consider in detail the error codes on the gas boiler of the Neva Suite.

Control Panel of the Gas Boiler Deluxe

e1.

Error E1. This fault indicates a low fluid pressure in the heating circuit.

Causes may be as follows:


e2.

Error E2. Unsuccessful ignition, check the following:


e6.

ERROR E6. No traction. Check out the possible causes of this fault:


e7.

ERROR E7. Excess the permissible temperature in the coolant.

What are the possible reasons and what to do we consider in more detail:


01

Error 01. Faults that occurred with unsuccessful ignition.

Possible reasons:


02

Error 02. Specifies the overheating of the boiler.

Possible reasons:


03

Error 03. In order to fix it, check:


04

Error 04. Low pressure in the heating circuit, you need to check:

  • Too reduced pressure in the heating systemRaise it to the recommended level.
  • Perhaps in the system formed air traffic, Using the air removal valve, delete it.
  • Broken pressure sensor In the heating circuit. Replace it.
  • Broken pump, clean it and, if necessary, replace. Spend a visual inspection of all connections and connectors on the control board.